A fortress, carefully repurposed.
Anlage 07 was dug into the Valais Alps in 1942. Our first hall opened in it in March 2025, with 100 % availability since.
From artillery to racks
The Swiss army built Anlage 07 to hold an artillery regiment through a siege. Tunnels, blast doors, air filtration and a spring kept it self-sufficient for months.
It was decommissioned in 1998. We bought it in 2022, kept the shell, the doors and the water, and rebuilt everything else for computing.

Inside Anlage 07
A slice through the mountain, from the portal to the halls.

- 1Portal and loading bay
- 2Generators, room for four
- 3Fuel, 72 h
- 4Transformers, UPS, batteries
- 5Cooling plant
- 6Hall 1, 120 racks
- 7Hall 2, from 2027
- 8Mountain water, about 10 °C
- 9Escape gallery
- 10Up to 120 m of granite

01 Power
Two feeds, each enough on its own.
Two 16 kV feeds arrive from two separate substations and run to two 2,000 kVA transformers in separate rooms. Each side carries the full load alone.
- 2N UPS, LFP batteries in fire-rated rooms
- 2 generators of 2,000 kVA, N+1
- 72 hours of fuel, plus a resupply contract
- Monthly load tests

02 Cooling
The mountain does the work.
Fissure water from the rock arrives at about 10 °C, and the granite around the halls stays at about 12 °C. Plate heat exchangers carry the heat away, so there are no chillers.
- Free cooling all year
- Heat exchangers and pumps, N+1
- Rear-door cooling up to 20 kW
- Water only below the floor, with leak detection and shut-off valves


03 Halls
One hall live, the next one on its way.
Hall 1 is its own fire compartment with gas suppression and early smoke detection. Hall 2 is being fitted out in the next cavern.
- Hall 1: 420 sq m, 120 racks
- Hall 2: 560 sq m, from 2027
- Inert gas suppression
- VESDA smoke detection

04 Site
Hard to reach, easy to work in.
A paved road leads to the portal building, which holds our offices and staff rooms. Inside the mountain there is a client room, a build room, a loading bay and storage.
- Loading bay, build room and storage
- Client room for your engineers
- A second escape gallery leads out from the halls
- Exact location shared with clients under contract
Technical specifications
- Design standard
- Tier III principles, not certified by Uptime Institute
- Rock cover
- Up to 120 m of granite
- White space
- 420 sq m today, 980 sq m from 2027
- IT capacity
- 1 MW today, 2.5 MW when built out
- Rack density
- 4 to 20 kW per rack
- Power feeds
- 2 × 16 kV from separate substations, 2 × 2,000 kVA dry-type transformers
- UPS
- 2N, lithium iron phosphate (LFP), sides A and B in separate rooms, about 10 min autonomy
- Generators
- 2 × 2,000 kVA, N+1, each in its own room (with Hall 2: 4 × 2,000 kVA, 3+1)
- Fuel
- 72 h at full load, about 25,000 L
- Cooling
- Mountain water at about 10 °C, plate heat exchangers, free cooling all year
- PUE
- 1.2 design, at full load
- Fire protection
- Inert gas, VESDA, separate compartments
- Blast protection
- Original 1940s fortress shell, rock and blast doors
- Connectivity
- 4 carriers over 2 separate fibre routes
- Availability
- 100 % since opening in March 2025

Clean power, reused heat
All our electricity is Swiss hydro. Waste heat warms the school and 30 homes in the village below.